Summary
The Danfoss AK-SM 8xxA Series has a stack-based buffer overflow (CVE-2026-129713) in a CGI handler that requires no authentication. The CVSS 4.0 score is 9.3 (critical).
What happened
A stack-based buffer overflow (CWE-121) in an unauthenticated CGI handler of the Danfoss AK-SM 8xxA Series controller allows remote attackers to send specially crafted HTTP/S POST requests. According to the description, this leads to memory corruption and a webserver restart, and hypothetically could allow arbitrary code execution with webserver privileges. No authentication is required to exploit the vulnerability.
Why it matters
The vulnerability is remotely exploitable over the network, with no authentication or user interaction. It has a CVSS 4.0 score of 9.3 (critical), assigned by Danfoss as CNA, with the vector CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N. Based on the available information, CISA's KEV catalog does not list it as actively exploited. The source does not indicate evidence that this was a zero-day.
Affected products and versions
Danfoss AK-SM8xxA, versions <= 5.4.0.
| Product | Versions | Fixed in |
|---|---|---|
| Danfoss AK-SM8xxA | <= 5.4.0 | — |
Action recommended by the source
The source does not state a fixed version or a specific mitigation in the available information. Consult the vendor's security advisory (Danfoss, DSA-2026-12-01): https://www.danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/danfoss-security-advisories/dsa-2026-12-01/
Sources and references
Weaknesses (CWE): CWE-121
Relevant change history
Published
Advisory published.